Cable Cervicom Interbus

Bus cable for data transmission systems (Interbus) in industrial processes in fixed installations.

See only CPR
See by cable type
See by fire behaviour

If you need technical support complete the form or call us at (+34) 937 362 730

Support
Cable Cervicom Interbus
~\ImgCli\FOTO2_1774.jpg
Bus cable for data transmission systems (Interbus) in industrial processes in fixed installations.
Protegido electromagneticas
No propagador de la llama
Interbus
Flexible
Desina
UL listed
Construction
1. Conductor
Stranded bare copper wires
Cross sectional area: 0,22mm2
2. Insulation
PE (Polyethylene)
Identification: Colours according to DIN 47100
(White+Brown, Green+Yellow, Grey+Pink)
3. Composition
Twisted pairs laid up together
4. Screen
Copper wire braid
5. Outer sheath
PVC (Polyvinyl chloride)
Colour: Violet according to DESINA
Technical characteristics
1. Operating voltage
250 V (Peak voltage)
*NOT suitable for power applications with direct connection to the mains power supply network.
2. Test Voltage
1500 V (conductor-conductor)
1000 V (conductor-screen)
3. Operating Tª (conductor)
-30°C +70°C
4. Min. bending radius
10xD
5. Conductor resistance
87,6 Ohm/Km
6. Mutual capacitance
60 pF/m
7. Characteristic Impedance
120 Ohm ± 20% (64kHz)
100 Ohm ± 15% (1MHz)
8. Insulation resistance
5 GOhm*Km Min.
9. Attenuation (dB/100m)
1,5 at 0,256 MHz
2,4 at 0,772 MHz
5,2 at 4 MHz
8,4 at 10 MHz
11,2 at 16 MHz
11,9 at 20 MHz
Standards / Properties
1. Reference standards
UL/CSA Type CMX according to UL 444 and CSA C22.2 No. 214-02
2. Flame Retardant
IEC 60332-1-2 / UL-1581 VW-1